ASEPTIC
RISK ZONE 2 : MODERATE INFECTION RISK
According to NFS90351 and ISO14644
- Particule cleanliness class : ISO8
- Particule Elimination Class : CP20
- Microbiological cleanliness class : M100
- New Air Rates : 6 vol/h
Brewing rate: greater than or equal to 10 volume/h
Differential pressure (positive or negative) : 15 Pa +ou- 5 Pa- Air flow rate of the area to be protected : Non-unidirectional flow
- Sound levels EN 15726
- Operating Room 48 dba / Hospitalization 40 dba / Radiology 48 dba / Laboratory 48 dba
Multizone DOPAIR - Mobile Unit for Air Decontamination
Functions
- Filtration (pre-filter + F7 + HEPA H14)
- Destruction of microorganisms thanks to photocatalysis technology
- Air flow speed up to 1200m3/h
- Touch screen multifunctions control panel (information on air quality, traceability, etc.)
- Extremely low sound level: 42 dB(A) at 720m3/h
Option : Fresh air kit
- Positive pressure
ROOM DOPAIR - MOBILE UNIT FOR AIR DECONTAMINATION
Functions
- Filtration (pre-filter + F7 + HEPA H14)
- Destruction of microorganisms thanks to photocatalysis technology
- Air flow speed up to 1200m3/h
- Touch screen multifunctions control panel (information on air quality, traceability, etc.)
- Extremely low sound level: 42 dB(A) at 800 m3/h
Option : Fresh air kit
- Positive pressure
DOPAIR2 - MOBILE UNIT FOR AIR DECONTAMINATION
Functions
- Triple filtration (pre-filter + F7 + HEPA H14)
- Destruction of microorganisms by photocatalysis or Bioxigen®
- Air flow speed up to 2500m3 / h
- Multifunctional touch control panel (information on air quality, traceability, etc.)
- Very low sound level: 39 dB (A) at 1,000 m3 / h
- Traceability: Recovery of the device data.
Options
- Positive pressure kit
- Tablet for remote control via WIFI
Option fresh air kit
- Positive pressure
DOPAIR - MOBILE UNIT FOR AIR DECONTAMINATION
Functions
-
- Filtration (F7 + HEPA H14)
- Destruction of microorganisms thanks to Bioxigen®
- Air flow speed up to 2000m3/h
- Control panel to adjust air flow speed and alarms display
- Very low sound level: 47 dB(A) at 1200 m3/h
Option fresh air kit
- Positive pressure
CLINICAIR 1B - COMPACT AND HYGIENIC AIR HANDLING UNIT
Functions
-
- Temperature control
- Humidity control
- Air renewal and air decontamination (filtration)
- Pressure in the room
- Air flow speed up to 2500 m3/h.
- Pressure up to 100 Pa
- Cooling system: direct expansion.
Clinicair 1B can be installed inside or at the nearest to the concerned area.
CLINICAIR 3 - COMPACT AND HYGIENIC AIR HANDLING UNIT
Functions
-
-
- Temperature control
- Humidity control
- Air renewal and air decontamination (filtration)
- Pressure in the room
- Air flow speed from 1000 to 20000 m3/h.
- Pressure up to 1500 Pa
- Cooling system: direct expansion or chilled water
-
Clinicair 3 can be installed at the nearest to the concerned area.
CLINICAIR 4 - COMPACT AND HYGIENIC AIR HANDLING UNIT
Functions
-
-
- Temperature control
- Humidity control
- Air renewal and air decontamination (filtration)
- Pressure in the room
- Air flow speed from 3000 to 8000 m3/h.
- Pressure up to 500 Pa
- Cooling system: direct expansion or chilled water.
-
Clinicair 4 can be installed in technical premises or outside the building.
ASEPTIC
RISK ZONE 3 : HIGH INFECTION RISK
According to NFS90351 and ISO14644
- Particular cleanliness class : ISO7
- Particle elimination class : CP10
- Microbiological cleanliness class : M10
New air rates : 6 vol/h- Brewing rate: greater than or equal to 15 volume/h
Differential pressure (positive or negative) : 15 Pa +ou- 5 Pa
Air flow rate of the area to be protected :
Unidirectional or non-unidirectional flow- Sound levels EN 15726
Operating Room 48 dba / Hospitalization 40 dba / Radiology 48 dba / Laboratory 48 dba
ROOM DOPAIR - UNITÉ MOBILE DE DÉCONTAMINATION D'AIR
Functions
- Filtration (pre-filter + F7 + HEPA H14)
- Destruction of microorganisms thanks to photocatalysis technology
- Air flow speed up to 1200m3/h
- Touch screen multifunctions control panel (information on air quality, traceability, etc.)
- Extremely low sound level: 42 dB(A) at 800 m3/h
Option : Fresh air kit
- Positive pressure
DOPAIR - MOBILE UNIT FOR AIR DECONTAMINATION
Functions
-
- Filtration (F7 + HEPA H14)
- Destruction of microorganisms thanks to Bioxigen®
- Air flow speed up to 2000m3/h
- Control panel to adjust air flow speed and alarms display
- Very low sound level: 47 dB(A) at 1200 m3/h
Option fresh air kit
- Positive pressure
CLINICAIR 1B - COMPACT AND HYGIENIC AIR HANDLING UNIT
Functions
-
- Temperature control
- Humidity control
- Air renewal and air decontamination (filtration)
- Pressure in the room
- Air flow speed up to 2500 m3/h.
- Pressure up to 100 Pa
- Cooling system: direct expansion.
Clinicair 1B can be installed inside or at the nearest to the concerned area.
CLINICAIR 3 - COMPACT AND HYGIENIC AIR HANDLING UNIT
Functions
-
-
- Temperature control
- Humidity control
- Air renewal and air decontamination (filtration)
- Pressure in the room
- Air flow speed from 1000 to 20000 m3/h.
- Pressure up to 1500 Pa
- Cooling system: direct expansion or chilled water
-
Clinicair 3 can be installed at the nearest to the concerned area.
CLINICAIR 4 - COMPACT AND HYGIENIC AIR HANDLING UNIT
Functions
-
-
- Temperature control
- Humidity control
- Air renewal and air decontamination (filtration)
- Pressure in the room
- Air flow speed from 3000 to 8000 m3/h.
- Pressure up to 500 Pa
- Cooling system: direct expansion or chilled water.
-
Clinicair 4 can be installed in technical premises or outside the building.
CENTRAL AIR TREATMENT UNITS – HVAC
Functions
HVAC are used in areas where it is necessary to control the temperature, humidity and filtration.
They are particularly intended for applications in hospitals, laboratories, food industry and the pharmaceutical industry. They were developed with particular care to reflect the specific needs of these environments.
HYPERASEPTIC
RISK ZONE 4 : VERY HIGH INFECTION RISK
According to NFS90351 and ISO14644
- Particular cleanliness class : ISO5
- Particle elimination class : CP5
- Microbiological cleanliness class : M1
New air rates : 6 vol/h- Brewing rate: Depending on the dimensioning of the filtering ceiling
Differential pressure (positive or negative) : 15 Pa +ou- 5 Pa
Air flow rate of the area to be protected :
Unidirectional flow- Sound levels EN 15726
Operating Room 48 dba / Hospitalization 40 dba / Pharmacy 45 dba
LAMINAR AIR FLOW CEILINGS
Functions
- A diffusing ceiling for effective protection of the clean area.
- Connected to the air handling cabinet and equipped with HEPA filters.
- Versions Mono-speed and Double-speed
CLINICAIR 3 - COMPACT AND HYGIENIC AIR HANDLING UNIT
Functions
-
-
- Temperature control
- Humidity control
- Air renewal and air decontamination (filtration)
- Pressure in the room
- Air flow speed from 1000 to 20000 m3/h.
- Pressure up to 1500 Pa
- Cooling system: direct expansion or chilled water
-
Clinicair 3 can be installed at the nearest to the concerned area.
CLINICAIR 4 - COMPACT AND HYGIENIC AIR HANDLING UNIT
Functions
-
-
- Temperature control
- Humidity control
- Air renewal and air decontamination (filtration)
- Pressure in the room
- Air flow speed from 3000 to 8000 m3/h.
- Pressure up to 500 Pa
- Cooling system: direct expansion or chilled water.
-
Clinicair 4 can be installed in technical premises or outside the building.
CENTRAL AIR TREATMENT UNITS – HVAC
Functions
HVAC are used in areas where it is necessary to control the temperature, humidity and filtration.
They are particularly intended for applications in hospitals, laboratories, food industry and the pharmaceutical industry. They were developed with particular care to reflect the specific needs of these environments.
ASEPTIC
MRI
According to NFS90351 and ISO14644
Objectives:
• Air conditioning of the technical room to the good power.
•
Air conditioning of the MRI room:
– Avoid the risk of asphyxiation and burning in case of leakage of helium in the gaseous state.
– Avoid overpressure related to this leak.
– Ensure air conditioning of the MRI room.
•
Cooling to the core of the MRI system, by chilled water:
– Have a safety system that automatically switches from chilled water to city water, without technical intervention.
– Avoid breakdowns and ensure the continuity of operation of the MRI
– Reduce costs associated with breakdowns and interventions
– Have a remote monitoring system for MRI handlers.
MRI HYDRAULIC KIT
The MRI hydraulic kit is a system of fluid cooler to cool down the MRI scan system with automatic management of a city water back up that enables to maintain the cooling conditions.
The MRI hydraulic kit is equipped with:
- A touch dialogue interface with display of information, alarms reports, mail sending service
- 4 temperature measurement points for water input / water output
- 2 water flow measurement points with minimum / maximum threshold and alarms
Main advantages:
- Mobility and speed of execution
- Industrialized equipment
- Maintenance
- Safety
CENTRAL AIR TREATMENT UNITS – HVAC
Functions
HVAC are used in areas where it is necessary to control the temperature, humidity and filtration.
They are particularly intended for applications in hospitals, laboratories, food industry and the pharmaceutical industry. They were developed with particular care to reflect the specific needs of these environments.